Input Signal
|
:
|
T.C : K、 S、 E、 J、 T、 B、 N RTD : Cu50、 Pt100 Linear voltage : 0- 5V,1-5V,0-10VDC Linear current : 0- 10mA, 4- 20mA (should connect external precision resistor, 500Ω for 0-10mA or 250Ω for 4-20mA) Extended signal: one input signal can be customized (Please advise the signal index no. when non-linear input)
|
Measure range
|
:
|
Thermocouple: K ( -50 ~ 1300℃ )、 S ( -50 ~ 1700℃ )、 T ( -200 ~ 350℃ ) 、 E ( 0 ~ 800℃ )、 J ( 0 ~ 1000℃ )、 B ( 300 ~ 1800℃ )、 N ( 0 ~ 1300℃ ) RTD: Cu50 ( -50 ~ 150℃ ) 、 Pt100 ( -200 ~ 600℃ )、 Cu100 ( -50 ~ 150℃ )
|
Linear input
|
:
|
-999 to +9999 defined by user.
|
Measure accuracy
|
:
|
0.2 grade when RTD, linear voltage, linear current, T.C input with free points cold junction compensation or copper resistance compensation)
0.2%FS±2.0℃ when T.C input with temperature compensation on cold-junction inside the meter
|
Respond time
|
:
|
≤0.5s when the filtering parameter FiL=0
|
Control way
|
:
|
On-off, Auto PID self-tuning, manual PID
|
Output Specification
|
:
|
Relay alarm outputs: 220VAC/2A, 220VAC/2A SSR voltage driving output: 12VDC0/30mA SCR contactless output: 100-240VAC/0.2A (continually), 2A(when 20mS, the repeated period time is more than 5S) Auxiliary power supply: 5VDC, 12VDC, 24VDC Linear current retransmission output: 4-20mA default or 0-10mA or customized Communication output: RS485, RS232 serial interface
|
Alarm Function
|
:
|
High limit, higher limit, low limit, lower limit, dFHA, dFLA , up to 4 alarm output.
|
Power Supply
|
:
|
85- 240VAC, -15%, +10% / 50- 60Hz; OR 24VDC/AC, -15%, +10%
|
Power Consumption
|
:
|
≤5W
|
Ambient Temperature
|
:
|
0- 50℃
|
Ambient Humidity
|
:
|
< 85%RH
|
Front Panel Dimension
|
:
|
96x96mm, 160x80mm, 80x160mm, 48x96mm, 96x48mm, 72x72mm, 48x48mm
|
Panel Cutout Dimension
|
:
|
92+0.5x 92+0.5mm, 45+0.5 x 92+0.5mm, 92+0.5×45+0.5mm, 152+0.5 x76+0.5mm, 76+0.5 x 152+0.5mm, 68+0.5 x 68+0.5mm, 45+0.5 x45+0.5mm.
|
Depth Mounting Surface
|
:
|
≤100mm.
|